Practical Experience of Using Additional Earthing of the Faulty Phase During a Ground Fault
Type
conference paper
Language
English
Original Abstract
The paper is focused on the operational experience with an automatic system for suppression of a fault current during a ground fault by the additional earthing of the faulted phase in a supply substation. Such system was experimentally installed in the Brno-Medlánky 110/22 kV substation. To verify the benefits of the system as well as to assess its possible failings, twenty-four experimental measurements based on a theoretical study were performed. During those experiments, low-resistance and arc ground faults were monitored in the urban and suburban part of the compensated network with a capacitive current of 300 A and 800 A. The results of the crucial experiments and the evaluation of the system functioning are summed up in the final part of the paper.
Keywords
ground fault, compensated, distribution network, earthing, shunt, residual current, faulty current, capacitive current
Authors
TOPOLÁNEK, D.; TOMAN, P.; ORSÁGOVÁ, J.; DVOŘÁK, J.
RIV year
2013
Released
16. 6. 2013
Publisher
IEEE
Location
Grenoble (France)
ISBN
978-1-4673-5667-1
Book
Ieee Proceedings Power Tech 2013
Pages from
1
Pages to
6
Pages count
BibTex
@inproceedings{BUT100322, author="David {Topolánek} and Petr {Toman} and Jaroslava {Orságová} and Jaromír {Dvořák}", title="Practical Experience of Using Additional Earthing of the Faulty Phase During a Ground Fault", booktitle="Ieee Proceedings Power Tech 2013", year="2013", pages="1--6", publisher="IEEE", address="Grenoble (France)", doi="10.1109/PTC.2013.6652291", isbn="978-1-4673-5667-1" }