Original Abstract
An alternative indicator of thermal response of radiant heating and cooling systems called heat storage efficiency (HSE) has been tested. The heat storage efficiency was compared with established indicators represented by the time constant tau(63), response time tau(95), and thermal energy stored (TES). The comparison was performed for three wall cooling systems with various combinations of pipe location, configuration of material layers, and materials of the thermal core. Considering the whole response curve (HSE) instead of focusing on one specific point on the curve (tau(63), tau(95)) allowed comparing the thermal response of complex systems by a single value. It also permitted predicting thermal response consistently regardless of the system and core material. Thermal energy stored predicted the thermal response of certain systems, but it may not be suitable for comparing the thermal response of radiant systems with different thermal admittance. Besides, a novel indicator of thermal output called effective thermal output (ETO) has been proposed. The effective thermal output considers both the steady-state thermal performance represented by the nominal thermal output and dynamic thermal performance represented by the heat storage efficiency. For thermally active building systems (TABS), effective thermal output was up to 57% lower than the nominal thermal output. (C) 2020 Elsevier B.V. All rights reserved.
Keywords
Radiant heating and cooling; Thermally active building systems (TABS); Thermal response; Response time; Heat storage efficiency; Effective thermal output; Thermal energy stored
Authors
KRAJČÍK, M.; ŠIKULA, O.
Released
15. 12. 2020
Publisher
Elsevier
Location
LAUSANNE
ISBN
0378-7788
Periodical
ENERGY AND BUILDINGS
Year of study
229
Number
1
State
Swiss Confederation
Pages from
Pages to
14
Pages count
URL
https://www.sciencedirect.com/science/article/pii/S037877882031937X
Full text in the Digital Library
http://hdl.handle.net/11012/208784
BibTex
@article{BUT166285, author="Michal {Krajčík} and Ondřej {Šikula}", title="Heat storage efficiency and effective thermal output: Indicators of thermal response and output of radiant heating and cooling systems", journal="ENERGY AND BUILDINGS", year="2020", volume="229", number="1", pages="1--14", doi="10.1016/j.enbuild.2020.110524", issn="0378-7788", url="https://www.sciencedirect.com/science/article/pii/S037877882031937X" }