Publication detail
Determination of air outlet C values by means of interferometry
JANOTKOVÁ, E. PAVELEK, M.
Original Title
Determination of air outlet C values by means of interferometry
Type
journal article - other
Language
English
Original Abstract
The basis for room air distribution solutions in ventilating and air conditioning rooms is the calcula-tion of velocities in air jets from supply outlets. To calculate velocities, the C-value of the air outlets must be known. The outlet C-values are specified for each type of outlet experimentally. The aim of this contribution is to acquaint readers with nontraditional methods for defining the C-value of an outlet from the angle of air jet expansion in the main jet zone, determined using interferometric visu-alization of the jet. To visualize the air jet from the outlet, a Mach-Zehnder interferometer is used which allows accurate, quality interferometric records to be obtained over the entire field of view of the jet. This contribution describes the dependence of the outlet C-value on the expansion angle of the main jet zone. The principles of interferometric measurements in transparent environments are dem-onstrated, along with their evaluation via special software developed for evaluating recorded inter-ferograms. The C-value of slot and rectangular outlets is determined using the method introduced here. Results demonstrate the high precision of the method, and that the C-values of outlets can be defined effectively from the visualization records.
Keywords
Air jets, velocity, supply air outlets, C-values, interferometry
Authors
JANOTKOVÁ, E.; PAVELEK, M.
RIV year
2006
Released
1. 3. 2006
Publisher
VEETECH Ltd.
ISBN
1473-3315
Periodical
The international journal of ventilation
Year of study
4
Number
4
State
United Kingdom of Great Britain and Northern Ireland
Pages from
311
Pages to
322
Pages count
12
BibTex
@article{BUT46678,
author="Eva {Janotková} and Milan {Pavelek}",
title="Determination of air outlet C values by means of interferometry",
journal="The international journal of ventilation",
year="2006",
volume="4",
number="4",
pages="311--322",
issn="1473-3315"
}