Sanace extrémně narušeného pláště chladící věže
English Title
Rehabilitation of extremely damaged shell of cooling tower
Type
conference paper
Language
Czech
Original Abstract
Efficient treatment of surface is necessary and crucial condition to achieve quality rehabilitation of reinforced concrete. The point is to remove all deteriorated and non-cohesive concrete to solid concrete. Generally required tensile strength of surface layers of treated surface concrete is 1,4 MPa. If the tensile strength of concrete cannot meet required value there is necessity to apply special rehabilitation technology to repair cooling towers. In case of thin structure of cooling towers the static load bearing capacity and stability of tower shell could be at risk.
Key words in English
rehabilitation, concrete, surface layers, cooling tower
Authors
RIV year
2004
Released
23. 11. 2004
Publisher
Česká stavební společnost
Location
Praha
ISBN
80-02-01683-1
Book
Sanace a rekonstrukce staveb 2004
Pages from
301
Pages to
307
Pages count
7