Publication detail

Analysis of PID Degraded Photovoltaic Power Plant

HYLSKÝ, J. STRACHALA, D. VANĚK, J.

Original Title

Analysis of PID Degraded Photovoltaic Power Plant

Type

conference paper

Language

English

Original Abstract

In this paper, the extent of PID (Potential Induced Degradation) impacts on a photovoltaic plant fitted with silicon-based modules is studied. In the first step, a PID degradation is diagnosed and confirmed by a thermal imager. Subsequently, the PV modules are uninstalled and transferred to an accredited workplace where are measured current-voltage characteristics. From these results, the maximum power - PMPP of PV modules is determined as a parameter indicating the extent of the PID degradation. The maximum dependence of the PMPP on the negative voltage potential concludes that the PID degradation range of the PV modules is not directly proportional to the negative voltage potential. These results are accompanied by the PV module electroluminescence measurement.

Keywords

Potential Induced Degradation, Photovoltaic power plant, Photovoltaic module

Authors

HYLSKÝ, J.; STRACHALA, D.; VANĚK, J.

Released

18. 10. 2017

Publisher

ECS Transaction

Location

USA

ISBN

978-80-214-5529-0

Book

Advanced Batteries Accumulators and Fuel Cells – 18 th ABAF

Edition

1

Edition number

1

ISBN

1938-5862

Periodical

ECS Transactions

Year of study

1

Number

81

State

United States of America

Pages from

185

Pages to

190

Pages count

6

BibTex

@inproceedings{BUT140301,
  author="Josef {Hylský} and Dávid {Strachala} and Jiří {Vaněk}",
  title="Analysis of PID Degraded Photovoltaic Power Plant",
  booktitle="Advanced Batteries Accumulators and Fuel Cells – 18
th ABAF",
  year="2017",
  series="1",
  journal="ECS Transactions",
  volume="1",
  number="81",
  pages="185--190",
  publisher="ECS Transaction",
  address="USA",
  doi="10.1149/08101.0185ecst",
  isbn="978-80-214-5529-0",
  issn="1938-5862"
}