Přístupnostní navigace
E-application
Search Search Close
Publication detail
TOMAN, P. DVOŘÁK, J. ORSÁGOVÁ, J. MIŠÁK, S.
Original Title
Experimental Measuring of the Earth Faults Currents in MV Compensated Networks
Type
conference paper
Language
English
Original Abstract
The MV compensated Networks in Czech Republic are operated as nonsymmetrical, that means as networks with non-transposed lines. In these networks the fault currents depend on the affected phase because the Petersen coil is tuned only for one value of earth current. The paper deals with influence of fault type on size of fault current and on the length of its transient phenomena. There are described experiments which were realized in distribution network held by E.ON Czech Republic. There were made a few different fault (low-impedance, spark gap arc, damaged MV cable, 1.6kOhm, 0.4kOhm and unearthed console of concrete tower) for three different places, for tuned and untuned Petersen coil and for some types of faults for all phases too, that means forty eight experimental faults. During each experiment the shunting of affected phase was applied.
Keywords
Earth Fault, Shunting Method, Compensated Networks Experimental Measurig
Authors
TOMAN, P.; DVOŘÁK, J.; ORSÁGOVÁ, J.; MIŠÁK, S.
RIV year
2010
Released
31. 3. 2010
Publisher
IET
Location
Manchester
ISBN
978-1-84919-212-5
Book
Proceedings of the IET 10th International Conference on Developments in Power System Protection
Edition
1
Edition number
Pages from
Pages to
5
Pages count
BibTex
@inproceedings{BUT37108, author="Petr {Toman} and Jaromír {Dvořák} and Jaroslava {Orságová} and Stanislav {Mišák}", title="Experimental Measuring of the Earth Faults Currents in MV Compensated Networks", booktitle="Proceedings of the IET 10th International Conference on Developments in Power System Protection", year="2010", series="1", number="1", pages="1--5", publisher="IET", address="Manchester", isbn="978-1-84919-212-5" }