Ripple Control Signal Using For Earth Fault Location In MV Networks

TOMAN, P. ORSÁGOVÁ, J.

Original Title

Ripple Control Signal Using For Earth Fault Location In MV Networks

Type

journal article - other

Language

English

Original Abstract

At present, digital protections using the admittance principle are able to identify quite reliably a single phase-to-ground connection and to determine the affected feeder. Still, the location of the fault presents a task yet to be solved. The main problem of a fault location consists is a low value of the fault current during a single phase-to-ground fault in com-pensated networks. This work started of an experiment performed in the second half of 2001. The experiment explored a possibility of the identification of a fault location in a circular network by means of ripple-control signal. The work deals with a novel method for a fault location that is able to determine the distance of a fault in a radial network (without a pos-sibility of a circular interconnection) using only values measured in a switching station. The principle of this method was published in 2000 [1]. It presents the application of the method in a real distribution network and the evaluation of the re-sults of this experiment.

Keywords

Power System, Earth Fault

Authors

TOMAN, P.; ORSÁGOVÁ, J.

RIV year

2005

Released

1. 1. 2005

Publisher

Slovak University of Technology

ISBN

1335-3632

Periodical

Journal of Electrical Engineering

Year of study

2005

Number

11-12

State

Slovak Republic

Pages from

313

Pages to

321

Pages count

9

BibTex

@article{BUT42238,
  author="Petr {Toman} and Jaroslava {Orságová}",
  title="Ripple Control Signal Using For Earth Fault Location In MV Networks",
  journal="Journal of Electrical Engineering
",
  year="2005",
  volume="2005",
  number="11-12",
  pages="9",
  issn="1335-3632"
}