Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním

TOPOLÁNEK, D. TOMAN, P. ORSÁGOVÁ, J.

Original Title

Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním

English Title

Influence of Compensated Distribution Network Operation with Wide Range on a Touch Voltage

Type

conference paper

Language

Czech

Original Abstract

This contribution is focused on evaluation of touch voltage quantity during a permanent ground fault in compensated distribution network with wide size of capacitive current 812 A. The touch voltage was evaluated near distribution transformer station 22/0.4 kV with the earthing system interconnected with the earthing of the neutral conductor of the LV network (0.4 kV). The data were recorded during real experiment, where low-impedance and arcing ground faults occurred. The fault was performed by conductive connection between faulty phase and iron part of the station which is connected to its earthing system. In this case, the fault current could achieve maximum quantity. (Influence of compensated distribution network operation with wide range on a touch voltage)

English abstract

This contribution is focused on evaluation of touch voltage quantity during a permanent ground fault in compensated distribution network with wide size of capacitive current 812 A. The touch voltage was evaluated near distribution transformer station 22/0.4 kV with the earthing system interconnected with the earthing of the neutral conductor of the LV network (0.4 kV). The data were recorded during real experiment, where low-impedance and arcing ground faults occurred. The fault was performed by conductive connection between faulty phase and iron part of the station which is connected to its earthing system. In this case, the fault current could achieve maximum quantity. (Influence of compensated distribution network operation with wide range on a touch voltage)

Keywords

ground fault; compensated; distribution network; touch voltage; distribution transformer station; capacitive current

Key words in English

ground fault; compensated; distribution network; touch voltage; distribution transformer station; capacitive current

Authors

TOPOLÁNEK, D.; TOMAN, P.; ORSÁGOVÁ, J.

RIV year

2011

Released

21. 9. 2011

Publisher

Technická univerzita Košice, Katedra elektroenergetiky

Location

Mäsiarska 74 042 00 Košice

ISBN

978-80-553-0724-4

Book

Proceedings of the 6th International Scientific Symposium on Electrical Power Engineering Elektroenergetika 2011

Pages from

253

Pages to

257

Pages count

5

BibTex

@inproceedings{BUT75153,
  author="David {Topolánek} and Petr {Toman} and Jaroslava {Orságová}",
  title="Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním",
  booktitle="Proceedings of the 6th International Scientific Symposium on Electrical Power Engineering Elektroenergetika 2011",
  year="2011",
  pages="253--257",
  publisher="Technická univerzita Košice, Katedra elektroenergetiky",
  address="Mäsiarska 74
042 00 Košice",
  isbn="978-80-553-0724-4"
}