Přístupnostní navigace
E-application
Search Search Close
Publication detail
MYŠKA, R. DREXLER, P.
Original Title
Simulation and Verification of Methods for Partial Discharge Source Localization
Type
conference paper
Language
English
Original Abstract
This article deals with possibilities of localization of partial discharges (PD) in oil power transformers. Localization can be performed by means of analysis of UHF waveforms which are measured during activity of the partial discharges. The time differences of arrival (TDOA) of the waveforms related to transient process occurrence in the signals are the main input parameters for localization methods. In order to estimate the position of the signal source in 3D space a minimum of four antennas has to be used, since the time of the PD occurrence is unknown. For localization purposes the system of nonlinear equations has to be solved. This can be performed by means of analytical or numerical methods. Both of the methods have their own advantages and disadvantages. The application of both approaches for signal source localization in measurement model will be presented in this paper. The methods will be compared in view of their suitability for a given configuration of antenna system.
Keywords
partial discharges, oil power transformers, time differences of arrival
Authors
MYŠKA, R.; DREXLER, P.
RIV year
2012
Released
27. 3. 2012
ISBN
978-1-934142-12-7
Book
Progress in Electromagnetics Research Symposium Proceedings, KL, Malaysia
Pages from
704
Pages to
708
Pages count
5
BibTex
@inproceedings{BUT91108, author="Radek {Myška} and Petr {Drexler}", title="Simulation and Verification of Methods for Partial Discharge Source Localization", booktitle="Progress in Electromagnetics Research Symposium Proceedings, KL, Malaysia", year="2012", pages="704--708", isbn="978-1-934142-12-7" }