Detail publikace

Evaluation of the Effect of Tube Pitch and Surface Alterations on Temperature Field at Sprinkled Tube Bundle

KRACÍK, P. COPEK, T. ZACHAR, M. POSPÍŠIL, J.

Originální název

Evaluation of the Effect of Tube Pitch and Surface Alterations on Temperature Field at Sprinkled Tube Bundle

Typ

článek ve sborníku ve WoS nebo Scopus

Jazyk

angličtina

Originální abstrakt

Water flowing on a sprinkled tube bundle forms three basic modes: It is the Droplet mode (liquid drips from one tube to another), the Jet mode (with an increasing flow rate droplets merge into a column) and the Membrane (Sheet) mode (with further increasing of falling film liquid flow rate columns merge and create sheets between the tubes. With sufficient flow rate sheets merge at this state and the tube bundle is completely covered by a thin liquid film). There are several factors influencing the individual mode types as well as heat transfer. Beside the above mentioned falling film liquid flow rate they are for instance tube diameters, tube pitches in a tube bundle or a physical condition of a falling film liquid. This paper presents a summary of data measured at atmospheric pressure at a tube bundle consisting of copper tubes of 12 milimeters diameter and of the studied tube length one meter. The tubes are positioned horizontally one above another with the tested pitches of 15, 20, 25 and 30 mm and there is a distribution tube placed above them with water flowing out. The thermal gradient of 15–40 has been tested with all pitches where the falling film liquid's temperature at the inlet of the distribution tube was 15 deg.C. The liquid was heated during the flow through the exchanger and the temperature of the sprinkled (heater) liquid at the inlet of the exchanger with a constant flow rate about 7.2 litres per minute was 40 deg.C. The tested flow of the falling film liquid ranged from 1.0 to 13.0 litres per minute. Sequences of 180 exposures have been recorded in partial flow rate stages by thermographic camera with record frequency of 30 Hz which were consequently assessed using the Matlab programme. This paper presents results achieved at the above mentioned pitches and at three types of tube bundle surfaces.

Klíčová slova

temperature field, sprinkled, thermovision measurements

Autoři

KRACÍK, P.; COPEK, T.; ZACHAR, M.; POSPÍŠIL, J.

Rok RIV

2015

Vydáno

6. 5. 2015

Nakladatel

EDP Sciences

Místo

Francie

ISSN

2100-014X

Periodikum

EPJ Web of Conferences

Ročník

92

Číslo

2015

Stát

Francouzská republika

Strany od

1

Strany do

8

Strany počet

8

Plný text v Digitální knihovně

BibTex

@inproceedings{BUT110702,
  author="Petr {Kracík} and Tomáš {Copek} and Martin {Zachar} and Jiří {Pospíšil}",
  title="Evaluation of the Effect of Tube Pitch and Surface Alterations on Temperature Field at Sprinkled Tube Bundle",
  booktitle="EPJ Web of Conferences",
  year="2015",
  journal="EPJ Web of Conferences",
  volume="92",
  number="2015",
  pages="1--8",
  publisher="EDP Sciences",
  address="Francie",
  doi="10.1051/epjconf/20159202039",