Přístupnostní navigace
E-přihláška
Vyhledávání Vyhledat Zavřít
Detail publikace
HIMR, D. HABÁN, V. DOKOUPIL, P.
Originální název
Check valve slam analysis in pumping station
Typ
článek ve sborníku ve WoS nebo Scopus
Jazyk
angličtina
Originální abstrakt
Pumping station supplies water for technological process. The check valve in the station was replaced with a new one. The regular test of black out discovered the high pressure pulsations accompanied with noticeable pipeline movement of discharge pipe. It was caused by late check valve closing, probably, when the back flow reached the highest possible velocity. This statement was supported with analysis of results of pressure measurement near the check valve and with a numerical simulation of the flow in the pipeline system.
Klíčová slova
water hammer, check valve
Autoři
HIMR, D.; HABÁN, V.; DOKOUPIL, P.
Vydáno
28. 3. 2016
Nakladatel
EDP Sciences
ISSN
2100-014X
Periodikum
EPJ Web of Conferences
Ročník
114
Číslo
2016
Stát
Francouzská republika
Strany od
1
Strany do
6
Strany počet
URL
http://www.epj-conferences.org/articles/epjconf/abs/2016/09/epjconf_efm2016_02038/epjconf_efm2016_02038.html
Plný text v Digitální knihovně
http://hdl.handle.net/11012/84112
BibTex
@inproceedings{BUT123443, author="Daniel {Himr} and Vladimír {Habán} and Pavel {Dokoupil}", title="Check valve slam analysis in pumping station", booktitle="EPJ Web of Conferences", year="2016", journal="EPJ Web of Conferences", volume="114", number="2016", pages="1--6", publisher="EDP Sciences", doi="10.1051/epjconf/201611402038", issn="2100-014X", url="http://www.epj-conferences.org/articles/epjconf/abs/2016/09/epjconf_efm2016_02038/epjconf_efm2016_02038.html" }