Utilization of an Air-PCM Heat Exchanger in Passive Cooling of Buildings: A Simulation Study on the Energy Saving Potential in Different European Climates

CHARVÁT, P. KLIMEŠ, L. ZÁLEŠÁK, M.

Originální název

Utilization of an Air-PCM Heat Exchanger in Passive Cooling of Buildings: A Simulation Study on the Energy Saving Potential in Different European Climates

Typ

článek v časopise ve Web of Science, Jimp

Jazyk

angličtina

Originální abstrakt

The energy saving potential (ESP) of passive cooling of buildings with the use of an air-PCM heat exchanger (cold storage unit) was investigated through numerical simulations. One of the goals of the study was to identify the phase change temperature of a PCM that would provide the highest energy saving potential under the specific climate and operating conditions. The considered air-PCM heat exchanger contained 100 aluminum panels filled with a PCM. The PCM had a thermal storage capacity of 200 kJ/kg in the phase change temperature range of 4 °C. The air-PCM heat exchanger was used to cool down the outdoor air supplied to a building during the day, and the heat accumulated in the PCM was rejected to the outdoors at night. The simulations were conducted for 16 locations in Europe with the investigated time period from 1 May–30 September. The outdoor temperature set point of 20 °C was used for the utilization of stored cold. In the case of the location with the highest ESP, the scenarios with the temperature set point and without the set point (which provides maximum theoretical ESP) were compared under various air flow rates. The average utilization rate of the heat of fusion did not exceed 50% in any of the investigated scenarios.

Klíčová slova

energy conservation; latent heat thermal energy storage; phase change materials; passive cooling

Autoři

CHARVÁT, P.; KLIMEŠ, L.; ZÁLEŠÁK, M.

Vydáno

22. 3. 2019

Nakladatel

MDPI

ISSN

1996-1073

Periodikum

ENERGIES

Ročník

12

Číslo

6

Stát

Švýcarská konfederace

Strany od

1

Strany do

17

Strany počet

17

URL

Plný text v Digitální knihovně

BibTex

@article{BUT156349,
  author="Pavel {Charvát} and Lubomír {Klimeš} and Martin {Zálešák}",
  title="Utilization of an Air-PCM Heat Exchanger in Passive Cooling of Buildings: A Simulation Study on the Energy Saving Potential in Different European Climates",
  journal="ENERGIES",
  year="2019",
  volume="12",
  number="6",
  pages="1--17",
  doi="10.3390/en12061133",
  issn="1996-1073",
  url="https://www.mdpi.com/1996-1073/12/6/1133"
}