Přístupnostní navigace
E-přihláška
Vyhledávání Vyhledat Zavřít
Detail publikace
PÍŠKA, J.
Originální název
Comparison of arc erosion coefficients
Typ
článek ve sborníku ve WoS nebo Scopus
Jazyk
angličtina
Originální abstrakt
The problem of nonunified approaches to giving arc erosion ratios is addressed for the application of molded case circuit breakers (MCCBs) in the range 6.5-10 kA. Charge, Joule’s integral and arc energy are compared as possible quantities to use for ratios of mass loss. The linearity of the relationship of mass loss to those quantities was used as the main metric. By this metric the ratio to charge was chosen as the most reliable one. But this relation was constant only for fixed contacts with arcrunners. For the moving contact, the mass loss ratio was a linear function of the effective value of the passing current.
Klíčová slova
arc erosion, MCCB, mass loss, erosion ratios
Autoři
Vydáno
23. 4. 2020
Nakladatel
Brno University of Technology, Faculty of Electrical Engineering and
Místo
Brno. Czech Republic
ISBN
978-80-214-5868-0
Kniha
Proceedings II of the 26th Conference STUDENT EEICT 2020
Edice
1.
Číslo edice
Strany od
95
Strany do
98
Strany počet
4
URL
https://www.fekt.vut.cz/conf/EEICT/archiv/sborniky/EEICT_2020_sbornik_2.pdf
BibTex
@inproceedings{BUT165308, author="Jakub {Píška}", title="Comparison of arc erosion coefficients", booktitle="Proceedings II of the 26th Conference STUDENT EEICT 2020", year="2020", series="1.", number="1.", pages="95--98", publisher="Brno University of Technology, Faculty of Electrical Engineering and", address="Brno. Czech Republic", isbn="978-80-214-5868-0", url="https://www.fekt.vut.cz/conf/EEICT/archiv/sborniky/EEICT_2020_sbornik_2.pdf" }