Detail publikace

Experimental Measuring of the Touch Voltages in Large Compensated Networks

TOMAN, P. TOPOLÁNEK, D. ORSÁGOVÁ, J. DVOŘÁK, J.

Originální název

Experimental Measuring of the Touch Voltages in Large Compensated Networks

Typ

článek ve sborníku ve WoS nebo Scopus

Jazyk

angličtina

Originální abstrakt

The paper describes the tests in real compensated distribution network with capacitive currents 300A and 800A. There were tested low-ohmic and arc fault. The first results show that the operation of large network is possible with using of the automatics of additional earthing of affected phase. The touch and step voltages were reduced under level allowed by standard EN 50522.

Klíčová slova

Fault currents, Power distribution faults, Fault diagnosis, Electrical safety, Touch voltage.

Autoři

TOMAN, P.; TOPOLÁNEK, D.; ORSÁGOVÁ, J.; DVOŘÁK, J.

Rok RIV

2012

Vydáno

11. 6. 2012

Nakladatel

Tallin University of Technology

Místo

Tallin

ISBN

978-1-4673-1978-2

Kniha

Proceedings of 2012 Electric Power Quality and Supply Reliability Conference

Edice

1

Číslo edice

1

Strany od

199

Strany do

204

Strany počet

319

BibTex

@inproceedings{BUT93436,
  author="Petr {Toman} and David {Topolánek} and Jaroslava {Orságová} and Jaromír {Dvořák}",
  title="Experimental Measuring of the Touch Voltages in Large Compensated Networks",
  booktitle="Proceedings of 2012 Electric Power Quality and Supply Reliability Conference",
  year="2012",
  series="1",
  number="1",
  pages="199--204",
  publisher="Tallin University of Technology",
  address="Tallin",
  isbn="978-1-4673-1978-2"
}