TOMAN, P. DVOŘÁK, J. ORSÁGOVÁ, J. TOPOLÁNEK, D.
Originální název
Using of Additional Earthing of Affected Phase for Limiting of The Touch Voltage During Earth Faults in MV Large Compensated Networks
Typ
článek ve sborníku ve WoS nebo Scopus
Jazyk
angličtina
Originální abstrakt
Distribution system operator (DSO) sometimes needs to operate the large network which means operating of the network with big capacitive current (in Czech Republic more than 800A). This operation puts the emphasis not only on the setting of the earth fault relays but on the safety of the point of fault too. The paper describes the theoretical analysis, simulation and tests in real compensated distribution network with capacitive current 820A. There were tested low-ohmic and arc fault.The first results show that this type of operation is possible with using of the automatics of additional earthing of affected phase. The touch and step voltages were reduced under level allowed by standard EN 50522
Klíčová slova
Earth fault; touch voltage; power system safety
Autoři
TOMAN, P.; DVOŘÁK, J.; ORSÁGOVÁ, J.; TOPOLÁNEK, D.
Vydáno
23. 4. 2012
Nakladatel
The Institution of Egineering and Technology
Místo
Birmingham
ISBN
978-1-84919-620-8
Kniha
Proceedings of IET Developments in Power System Protection 2012
Edice
1
Číslo edice
Strany od
Strany do
5
Strany počet
300
BibTex
@inproceedings{BUT93453, author="Petr {Toman} and Jaromír {Dvořák} and Jaroslava {Orságová} and David {Topolánek}", title="Using of Additional Earthing of Affected Phase for Limiting of The Touch Voltage During Earth Faults in MV Large Compensated Networks", booktitle="Proceedings of IET Developments in Power System Protection 2012", year="2012", series="1", number="1", pages="1--5", publisher="The Institution of Egineering and Technology", address="Birmingham", doi="10.1049/cp.2012.0101", isbn="978-1-84919-620-8" }