An earth fault location method based on negative sequence voltage changes at low voltage side of distribution transformers
Typ
článek v časopise ve Web of Science, Jimp
Jazyk
angličtina
Originální abstrakt
The paper presents a new approach for earth fault localization which is based on evaluation of phase to ground voltages recorded by voltage monitors installed at low-voltage side of distribution transformer station deployed under smart metering projects. The introduced method "Vdip" determines the probability of asymmetrical fault location based on comparison of the changes in negative sequence current recorded at the feeding medium voltage substation and changes in negative sequence voltages recorded at the LV sides of distribution transformers. The paper describes the nature of the method and presents its principle using simulation of a MV resonant earthed distribution network where short-term connection of an auxiliary resistor is used. The method was also evaluated in real resonant earthed 22 kV network, where totally 15 earth faults with fault resistance up to 1.2 k Omega were carried out. As the result of this field test, the location error of the Vdip method is presented.
Klíčová slova
Earth fault; Fault localization; Voltage monitor; Distribution network; Negative sequence voltage; Distribution transformer; Voltage dip
Autoři
TOPOLÁNEK, D.; LEHTONEN, M.; TOMAN, P.; ORSÁGOVÁ, J.; DRÁPELA, J.
Vydáno
1. 6. 2020
Nakladatel
ELSEVIER SCI LTD
Místo
OXFORD
ISSN
0142-0615
Periodikum
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS
Ročník
118
Číslo
Stát
Spojené království Velké Británie a Severního Irska
Strany od
1
Strany do
8
Strany počet
URL
https://www.sciencedirect.com/science/article/pii/S014206151932068X?dgcid=author
BibTex
@article{BUT161008, author="David {Topolánek} and Matti {Lehtonen} and Petr {Toman} and Jaroslava {Orságová} and Jiří {Drápela}", title="An earth fault location method based on negative sequence voltage changes at low voltage side of distribution transformers", journal="INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS", year="2020", volume="118", number="118", pages="1--8", doi="10.1016/j.ijepes.2019.105768", issn="0142-0615", url="https://www.sciencedirect.com/science/article/pii/S014206151932068X?dgcid=author" }