Přístupnostní navigace
E-přihláška
Vyhledávání Vyhledat Zavřít
Detail publikace
TOMAN, P. DRÁPELA, J. ORSÁGOVÁ, J.
Originální název
Solution of Voltage Asymmetry and Reduction of Outage Time in MV Compensated Networks
Typ
článek ve sborníku ve WoS nebo Scopus
Jazyk
angličtina
Originální abstrakt
The compensated networks are affected by the phase capacity asymmetry of wiring, which causes the unbalancing of the phase voltages in the tuned condition of the arc-suppression coil. In the especially unfavourable cases this effect reduces the possibility of network operation with the tuned arc-suppression coil. The operation with the arc-suppression coil out of tune is accompanied by higher values of the fault currents during the ground faults and the natural frequency of the course of recovery voltage in the network after switching off or interrupting the ground fault. These disadvantages can only be removed by efficient elimination of the phase asymmetry. The new methods of eliminating the phase capacity asymmetry allow for controlling the phase asymmetry size (its reduction as well as its possible increase), they keep it within a specified tolerance band (Uo value in the tuned condition of the arc-suppression coil is typically maintained at levels from 1% to 4% of the network voltage phase value). The new methods of elimination of the phase capacity asymmetry have favourable effects on the network operation during the ground fault and do not reduce the protecting elements sensitivity to high-ohm ground faults. By improving the accuracy of the arc-suppression coil tuning the safety of the compensated networks operation can be enhanced. The other properties of the whole system of phase capacity asymmetry elimination designed to increase the compensated networks operation safety, to improve the reliability of ground-fault protections and to locate the fault areas, can be fully utilized.
Klíčová slova
voltage asymmetry, outage time reduction
Autoři
TOMAN, P.; DRÁPELA, J.; ORSÁGOVÁ, J.
Rok RIV
2008
Vydáno
28. 9. 2008
Nakladatel
IEEE
Místo
Wollongong, AUSTRALIA
ISBN
978-1-4244-1771-1
Kniha
2008 13TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, VOLS 1 AND 2
Edice
1
Číslo edice
Strany od
461
Strany do
467
Strany počet
7
BibTex
@inproceedings{BUT26748, author="Petr {Toman} and Jiří {Drápela} and Jaroslava {Orságová}", title="Solution of Voltage Asymmetry and Reduction of Outage Time in MV Compensated Networks", booktitle="2008 13TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, VOLS 1 AND 2", year="2008", series="1", number="1", pages="461--467", publisher="IEEE", address="Wollongong, AUSTRALIA", doi="10.1109/ICHQP.2008.4668818", isbn="978-1-4244-1771-1" }