Originální abstrakt

The compensated networks are affected by the phase capacity asymmetry of wiring, which causes the unbalancing of the phase voltages in the tuned condition of the arc-suppression coil. In the especially unfavourable cases this effect reduces the possibility of network operation with the tuned arc-suppression coil. The operation with the arc-suppression coil out of tune is accompanied by higher values of the fault currents during the ground faults and the natural frequency of the course of recovery voltage in the network after switching off or interrupting the ground fault. These disadvantages can only be removed by efficient elimination of the phase asymmetry. The new methods of eliminating the phase capacity asymmetry allow for controlling the phase asymmetry size. The new methods of elimination of the phase capacity asymmetry have favourable effects on the network operation during the ground fault and do not reduce the protecting elements sensitivity to high-ohm ground faults. By improving the accuracy of the arc-suppression coil tuning the safety of the compensated networks operation can be enhanced. The other properties of the whole system of phase capacity asymmetry elimination designed to increase the compensated networks operation safety, to improve the reliability of ground-fault protections and to locate the fault areas, can be fully utilized.

Klíčová slova

Power systems, Fault location

Autoři

TOMAN, P.; PAAR, M.; ORSÁGOVÁ, J.

Rok RIV

2007

Vydáno

19. 9. 2007

Nakladatel

TU Košice

Místo

Košice

ISBN

978-80-553-0400-7

Kniha

PROCEEDINGS OF THE IVTH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRIC POWER ENGINEERING - ELEKTROENERGETIKA 2007

Edice

1

Číslo edice

1

Strany od

420

Strany do

423

Strany počet

4

BibTex

@inproceedings{BUT27994,
  author="Petr {Toman} and Martin {Paar} and Jaroslava {Orságová}",
  title="Elimination of Phase Capacity Asymmetry and Localization of Faults in Compensated Networks",
  booktitle="PROCEEDINGS OF THE IVTH INTERNATIONAL SCIENTIFIC SYMPOSIUM ON ELECTRIC POWER ENGINEERING - ELEKTROENERGETIKA 2007",
  year="2007",
  series="1",
  number="1",
  pages="420--423",
  publisher="TU Košice",
  address="Košice",
  isbn="978-80-553-0400-7"
}