Detail publikace

Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním

TOPOLÁNEK, D. TOMAN, P. ORSÁGOVÁ, J.

Originální název

Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním

Anglický název

Influence of Compensated Distribution Network Operation with Wide Range on a Touch Voltage

Typ

článek ve sborníku ve WoS nebo Scopus

Jazyk

čeština

Originální abstrakt

This contribution is focused on evaluation of touch voltage quantity during a permanent ground fault in compensated distribution network with wide size of capacitive current 812 A. The touch voltage was evaluated near distribution transformer station 22/0.4 kV with the earthing system interconnected with the earthing of the neutral conductor of the LV network (0.4 kV). The data were recorded during real experiment, where low-impedance and arcing ground faults occurred. The fault was performed by conductive connection between faulty phase and iron part of the station which is connected to its earthing system. In this case, the fault current could achieve maximum quantity. (Influence of compensated distribution network operation with wide range on a touch voltage)

Anglický abstrakt

This contribution is focused on evaluation of touch voltage quantity during a permanent ground fault in compensated distribution network with wide size of capacitive current 812 A. The touch voltage was evaluated near distribution transformer station 22/0.4 kV with the earthing system interconnected with the earthing of the neutral conductor of the LV network (0.4 kV). The data were recorded during real experiment, where low-impedance and arcing ground faults occurred. The fault was performed by conductive connection between faulty phase and iron part of the station which is connected to its earthing system. In this case, the fault current could achieve maximum quantity. (Influence of compensated distribution network operation with wide range on a touch voltage)

Klíčová slova

ground fault; compensated; distribution network; touch voltage; distribution transformer station; capacitive current

Klíčová slova v angličtině

ground fault; compensated; distribution network; touch voltage; distribution transformer station; capacitive current

Autoři

TOPOLÁNEK, D.; TOMAN, P.; ORSÁGOVÁ, J.

Rok RIV

2011

Vydáno

21. 9. 2011

Nakladatel

Technická univerzita Košice, Katedra elektroenergetiky

Místo

Mäsiarska 74 042 00 Košice

ISBN

978-80-553-0724-4

Kniha

Proceedings of the 6th International Scientific Symposium on Electrical Power Engineering Elektroenergetika 2011

Strany od

253

Strany do

257

Strany počet

5

BibTex

@inproceedings{BUT75153,
  author="David {Topolánek} and Petr {Toman} and Jaroslava {Orságová}",
  title="Vliv provozu kompenzované sítě velkého rozsahu na velikost dotykového napětí u DTS se společným uzemněním",
  booktitle="Proceedings of the 6th International Scientific Symposium on Electrical Power Engineering Elektroenergetika 2011",
  year="2011",
  pages="253--257",
  publisher="Technická univerzita Košice, Katedra elektroenergetiky",
  address="Mäsiarska 74
042 00 Košice",
  isbn="978-80-553-0724-4"
}