Přístupnostní navigace
E-application
Search Search Close
Publication detail
TOMAN, P. ORSÁGOVÁ, J.
Original Title
Location of The Ground Faults in MV Networks
Type
journal article - other
Language
English
Original Abstract
The paper describes new method of elimination phase capacitance asymmetry by ancillary suppression coils. This method has favorable effects on the network operation during the ground fault and do not reduce the protecting elements sensitivity to high-ohm ground faults. By improving the accuracy of the arc-suppression coil tuning the safety of the compensated networks operation can be enhanced. The new method of elimination of the phase asymmetry opens the secondary advantage like new method of fault location. This location method starts from idea of fault location using inter-harmonic signal or remote control signal and is based on injection of higher inter-harmonic frequency signal to the secondary windings of ancillary suppression coil which is connected to affected phase
Keywords
ground fault, fault localtion
Authors
TOMAN, P.; ORSÁGOVÁ, J.
RIV year
2008
Released
14. 5. 2008
ISBN
0204-3599
Periodical
Technična elektrodynamika
Year of study
Number
388
State
Ukraine
Pages from
38
Pages to
41
Pages count
4
BibTex