Přístupnostní navigace
E-přihláška
Vyhledávání Vyhledat Zavřít
Detail publikace
TOMAN, P. ORSÁGOVÁ, J.
Originální název
Location of The Ground Faults in MV Networks
Typ
článek v časopise - ostatní, Jost
Jazyk
angličtina
Originální abstrakt
The paper describes new method of elimination phase capacitance asymmetry by ancillary suppression coils. This method has favorable effects on the network operation during the ground fault and do not reduce the protecting elements sensitivity to high-ohm ground faults. By improving the accuracy of the arc-suppression coil tuning the safety of the compensated networks operation can be enhanced. The new method of elimination of the phase asymmetry opens the secondary advantage like new method of fault location. This location method starts from idea of fault location using inter-harmonic signal or remote control signal and is based on injection of higher inter-harmonic frequency signal to the secondary windings of ancillary suppression coil which is connected to affected phase
Klíčová slova
ground fault, fault localtion
Autoři
TOMAN, P.; ORSÁGOVÁ, J.
Rok RIV
2008
Vydáno
14. 5. 2008
ISSN
0204-3599
Periodikum
Technična elektrodynamika
Ročník
Číslo
388
Stát
Ukrajina
Strany od
38
Strany do
41
Strany počet
4