Přístupnostní navigace
E-přihláška
Vyhledávání Vyhledat Zavřít
Detail publikace
Zdeněk NĚMEC, Radomil MATOUŠEK, Ladislav BÉBAR, Tomáš PAŘÍZEK
Originální název
AUTOMATIC CONTROL OF NITROGEN OXIDES REDUCTION DURING WASTE COMBUSTION
Typ
článek ve sborníku ve WoS nebo Scopus
Jazyk
angličtina
Originální abstrakt
The paper summarizes knowledge acquired from analysis of automatic control of municipal solid waste incinerator plant. The analysis is concerned with non-catalytic reduction of nitrogen oxides (NOx) in the combustion products by means of injection of ammonia water solution (NH4OH) into the upper part of boiler hearth. An automatic control is used for ammonia’s dosing. Objective of this control is to keep NOx level in the combustion products below the ecological limit. The base of a standard control is a proportional-integrative (PI) controller. It was discovered during the analysis that for the given process the integrative component isn’t suitable. It is because the ammonia reducing potential is limited.
Klíčová slova
Municipal waste incinerator plant, nitrogen oxides (NOx), non-catalytic reduction of nitrogen oxides, ammonia water solution (NH4OH), and automatic control.
Autoři
Rok RIV
2006
Vydáno
27. 8. 2006
Nakladatel
Process Engineering Publisher, Praha, Czech republik
Místo
Praha, Czech Republic
ISBN
80-86059-45-6
Kniha
CHISA 2006
Strany od
P5.082
Strany počet
5